74.0cm W x 83.5cm H x 75.9cm D (29.1" W x 32.9" H x 29.9" D)
| Item | NAA17V60 | |
|---|---|---|
| Cooling capacity | 4 - 5 TON | |
| Unit | Dimensions | 74.0cm W x 83.5cm H x 75.9cm D (29.1" W x 32.9" H x 29.9" D) |
| Net weight | 83.9 kg (185 lbs) | |
| Gross weight | 97.1 kg (214 lbs) | |
| Sound rating level (dBA) | 0 dBA | |
| Electrical data | Volts Phase Hz | 230 - 1 60 |
| Minimum circuit ampacity (A) | 30 Amps | |
| Max. overcurrent protection (A) | 45 Amps | |
| Volts (V) min - max | 187 - 253 | |
| Compressor | Compressor type | Inverter driven rotary |
| Hz | 18 - 78 | |
| Rated current (RLA) | 20 Amps | |
| LRA | 58.1 Amps | |
| Fan motor | Power supply | DC |
| RLA (A) | 1.8 | |
| Maximum speed (rpm) | 1,100 RPM | |
| Fan Motor HP | 1/4 | |
| FLA (A) | 1.8 Amps | |
| Coil | Number of rows | 2 |
| Tube outside diameter | 9/32" | |
| Tube pitch x row pitch | 21.08 mm x 13.46 mm (0.8 inch x 0.5 inch) | |
| Net face area | 18.35 sq. ft. | |
| Refrigerant | Refrigerant type | R454B |
| Liquid line OD | 3/8" (9.5 mm) | |
| Vapor line OD | 7/8" (22.2 mm) | |
| Refrigerant charge (oz) | 4,399.8 g (155.2 oz) | |
| Max line length | 100 ft | |
| Max vertical lift | 50 ft | |
| Operating temperature | Cooling mode | -15 - 51.11 °C |
| EER2 | Up to 11.5* | |
| Certifications | AHRI, cETLus | |
*With select AHRI matched indoor equipment.
1 Energy Efficiency Ratio; Certified per AHRI 210/240
2 Seasonal Energy Efficiency Ratio; Certified per AHRI 210/240
3 Heating Seasonal Performance Factor; Certified per AHRI 210/240
Navien reserves the right to change specifications at any time without prior notice.